Manufactured in the USA  ·  Est. 1952

VB 10-40 Electric Steam Generators

VB-25 25 Kilowatt (kW) Rating High Pressure Electric Steam Generator

VB-25 25 kW Rating High Pressure Electric Steam Generator

Dimensions

Length25 in
Width
(No Options)
18 in
Width
(with MAFD option)
25 in
Height25 in

Minimum Clearance

Total Length40 in
Total Width25 in
Total Height26 in

Industry Standards

  • American Society of Mechanical Engineers (ASME) - Boiler and Pressure Vessel Code
  • American Society of Mechanical Engineers (ASME) - CSD-1
  • Canadian Underwriters Laboratories (cUL)
  • Underwriters Laboratories (UL)
ASMEUL Listed

Standard Features

ASME CertifiedHigh Pressure Safety Reset
UL Listed and labeled under UL 834Dual Pressure Controls (UL 353)
Low Level Cut-Off (LLCO) (UL 353)Safety Relief Valve possessing the ASME V Mark

Recommended Options (Non-Standard)

Spare Parts PackageMotorized Automatic Flush and Drain (MAFD)

Specifications

BrandsElectro-Steam™
Electrical Power25 kW
Power Supply Voltage1208 VAC, 230 VAC, 380 VAC, 415 VAC, 440 VAC, 480 VAC, 600 VAC
Phase3
Frequency50 Hz, 60 Hz
Boiler Horse Power2.5 bhp
Steam Capacity286.25 lb/hr (39.12 kg/hr)
Water Consumption10.34 gal/hr (39.12 L/hr)
Gross British Thermal Units (BTU) Output83,688 Btu/hr
Maximum Boiler Pressure100 psi
Operating Pressure0 to 80 psi
Note for Operating PressureFactory Set at 80 psi
Maximum Boiler Capacity6 gal
Boiler Fill Capacity4.2 gal
Boiler Material3Carbon Steel
Cabinet Material304 Stainless Steel
Plumbing MaterialBrass, Carbon Steel (Schedule 40)

Amperage by Voltage (3Ø Phase)

208 VAC 240 VAC 380 VAC 415 VAC 440 VAC 480 VAC 600 VAC
69.40 A 65.50 A 38.00 A 34.80 A 32.80 A 30.10 A 24.00 A

Plumbing Connection Sizes

Water Inlet3/8" NPT (National Pipe Thread) (Female) - Y-Strainer, Brass
Steam Outlet1/2" NPT (National Pipe Thread) (Female) - Ball Valve, Brass
Safety Valve3/4" NPT (National Pipe Thread) (Female) - Safety Valve, Brass
Drain3/4" National Pipe Thread (NPT) (Female) - Ball Valve, Brass
Additional Drain (Motorized Automatic Flush and Drain (MAFD) Option Included)3/4" NPT (National Pipe Thread) (Female) - Motorized Valve, Brass

Options

Spare Parts Package Includes 18-Month Warranty (12-Month Standard)
(2) Electric Heaters and (2) Heater Gaskets
(2) Sight Glass Tubes and (4) Washers
(1) Pressure Control
(1) Contactor
Manual Low Water Reset4 Manual Low Water Reset trips if the electric heaters shut-off because of a low water condition. Reset must be manually pressed to resume steam production.
  • 1 Each Electro-Steam™ electric steam generator requires two (2) power supplies: One (1) customer specific primary high voltage supply for the heaters and one (1) secondary 120 VAC 1Ø, 50/60 Hz supply for the Controls.
  • 2 Calculations are based off of a 212 ºF boiler feed-water temperature. Boiler feed-water temperatures that range between 60 ºF and 140 ºF, are approximately 80% to 90% of the calculated values shown. Boiler feed-water must not exceed 140 ºF.
  • 3 Wetted Surfaces
  • 4 A Manual Low Water Reset Button is supplied standard with every steam generator, but it is disabled. If this Reset Button is required as per your local boiler codes, simply plug the two attached wires into the PC-Board terminals labeled "Reset".
Free Resource
Conveyor Belt Cleaning Solutions eBook cover

Conveyor Belt Cleaning Solutions for the Food & Beverage Industry

Learn how all-electric dry steam sanitation is transforming hygiene standards across food processing and beverage operations. Download our free industry guide.

Download Free eBook
Get in Touch

Ready to Find the Right Steam Solution?

Our engineering team is here to help you select the right generator for your application. Custom specifications, expert guidance, same-day part shipping.