DS 150-480 Electric Steam Generators

DS-150 (H) 150 Kilowatt (kW) Double Stack High Pressure Electric Steam Generator

DS-150 (H), 150 Kilowatt (kW) Double Stack High Pressure Electric Steam Generator

Dimensions

Length64 in
Width38 in
Height63 in

Minimum Clearance

Total Length125 in
Total Width60 in
Total Height70 in

Industry Standards

  • American Society of Mechanical Engineers (ASME) - Boiler and Pressure Vessel Code
  • American Society of Mechanical Engineers (ASME) - CSD-1
  • Canadian Underwriters Laboratories (cUL)
  • Underwriters Laboratories (UL)
ASMEUL Listed

Standard Features

ASME CertifiedHigh Pressure Safety Reset
UL Listed and labeled under UL 834Dual Pressure Controls (UL 353)
Low Level Cut-Off (LLCO) (UL 353)Safety Relief Valve possessing the ASME V Mark
Single Service Transformer

Recommended Options (Non-Standard)

Motorized Automatic Flush and Drain (MAFD)Spare Parts Package
5-Micron Water Filter

Specifications

Brands Electro-Steam™
Electrical Power 150 kW (75 kW per Box) (2 Boxes)
Alternating Current (AC) Voltage1 208 V, 230 V, 360 V, 400 V, 480 V, 600 V
Phase 3
Frequency 50 Hz, 60 Hz
Boiler Horse Power 15 bhp (7.5 bhp per Boiler)
Steam Capacity2 517.5 lb/hr (234.0 kg/hr)
Average Water Consumption3 62.01 gal/hr (234.0 L/hr)
Gross British Thermal Units (BTU) Output4 502,080 Btu/hr
Maximum Boiler Pressure 100 psi
Operating Pressure 0 to 80 psi
Note for Operating Pressure Factory Set at 80 psi
Maximum Boiler Capacity 53 gal
Note for Maximum Boiler Capacity 26.5 Gallons per Boiler
Boiler Fill Capacity 44 gal
Note for Boiler Fill Capacity 22.0 Gallons per Boiler
Boiler Material5 Carbon Steel
Cabinet Material 304 Stainless Steel
Plumbing Material6 Brass (Schedule 40), Carbon Steel (Schedule 40)

Amperage by Voltage (3Ø Phase)

208 VAC 230 VAC 360 VAC 400 VAC 480 VAC 600 VAC
416.4 A
(208.2 A per Box)
(2 Boxes)
392.9 A
(196.5 A per Box)
(2 Boxes)
253.6 A
(126.8 A per Box)
(2 Boxes)
226.5 A
(113.2 A per Box)
(2 Boxes)
180.4 A
(90.21 A per Box)
(2 Boxes)
144.3 A
(72.17 A per Box)
(2 Boxes)

Plumbing Connection Sizes

Water Inlet (Shared)1/2" NPT (Female) - Y-Strainer, Brass
Steam Outlet (Shared)6" Flange (150 psi, 4-Hole) - 2-1/2" pipe connection
Safety Valves (x2)(Separate)1-1/4" NPT (Male) (x2) - Two Black Pipes routed to the floor; one from each Safety Valve.
Drain + MAFD Option (Shared)1" NPT (Female) - Elbow, Brass
Steam Trap (Not Included)3/4" NPT (Female) - Threaded connection on the bottom of the 2-1/2" shared Steam Outlet pipe.

Included Options

Single Service Transformer7 Two of these options are supplied standard in all double stack steam generators; the Transformer steps down the primary high voltage supplied for the heaters, in order to provide 120VAC 1Ø for the controls; with this option, only the two (2) primary high voltage supplies are required.
Manual Low Water Reset8 Manual Low Water Reset trips if the electric heaters shut-off because of a low water condition. Reset must be manually pressed to resume steam production.
Water Feed Booster Pump Two Water Feed Booster Pumps are supplied standard in all high-pressure double stack steam generators. Each Water Feed Booster Pump increases the incoming water pressure to overcome the operating pressure of each steam generator. Each Booster Pump requires a 5-150 psi water supply with a minimum flow rate of 3 gpm (At least 6 gpm is required for both)

Options

Motorized Automatic Flush and Drain (MAFD) During Start-Up before steam pressure is accumulated, the Motorized Automatic Flush and Drain option cycles fresh water through the boiler for 0-300 seconds (Factory set for 180 seconds or three (3) minutes). As old water is drained out, fresh water will be cycled in. This drain valve will not open if boiler pressure exceeds 5 psi, and the electric heaters are locked out during flush cycle.
Spare Parts Package Includes 18-Month Warranty (12-Month Standard)
(2) Electric Heaters & (2) Heater Gaskets
(2) Sight Glass Tubes & (4) Washers
(1) Pressure Control
(1) Contactor
5-Micron Water Filter 2-stage, 5-micron water filter installed into incoming water line to reduce sediment, dirt, rust, chlorine, and even odor from incoming water supply.
  • 1 Electro-Steam™ Double Stack electric steam generators are two (2) electric steam boilers stacked inside one (1) cabinet. They are plumbed together, but not wired together. Double Stack steam generators require two (2) or four (4) customer specific high voltage feeds, one (1) per Electrical Box - 150 kW models have two (2) Electrical Boxes to feed and 200 to 480 kW models have four (4).
  • 2 Calculated values are based off of a 212ºF boiler feed-water temperature. However, it must not exceed 140ºF. Temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated values shown.
  • 3 Calculated values are based off of a 212ºF boiler feed-water temperature. However, it must not exceed 140ºF. Temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated values shown.
  • 4 Calculated values are based off of a 212ºF boiler feed-water temperature. However, it must not exceed 140ºF. Temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated values shown.
  • 5 Wetted Surfaces.
  • 6 Wetted Surfaces.
  • 7 Two (2) Single Service Transformer options are included with each double stack electric steam generator. These options provide 120 VAC 1Ø, 50/60 Hz for each boiler's controls.
  • 8 A Manual Low Water Reset Button is supplied standard with every steam generator, but it is disabled. If this Reset Button is required as per your local boiler codes, simply plug the two attached wires into the PC-Board terminals labeled "Reset"
Free Resource
Conveyor Belt Cleaning Solutions eBook cover

Conveyor Belt Cleaning Solutions for the Food & Beverage Industry

Learn how all-electric dry steam sanitation is transforming hygiene standards across food processing and beverage operations. Download our free industry guide.

Download Free eBook
Get in Touch

Ready to Find the Right Steam Solution?

Our engineering team is here to help you select the right generator for your application. Custom specifications, expert guidance, same-day part shipping.